Table 1: Reduxi standard telegram structure for Iskraemeco AM550 DLMS push on P1 interface.
No. | OBIS | Name | Unit | Refresh time |
1. | 0-0:96.1.1 | Serial number of meter | / | 1 second |
2. | 1-0:1.7.0 | Positive active instantaneous power (A+) | W | 1 second |
3. | 1-0:2.7.0 | Negative active instantaneous power (A-) | W | 1 second |
4. | 1-0:3.7.0 | Positive reactive instantaneous power (R+) | VAr | 1 second |
5. | 1-0:4.7.0 | Negative reactive instantaneous power (R-) | VAr | 1 second |
6. | 1-0:1.8.0 | Positive active energy (A+) total | Wh | 1 second |
7. | 1-0:2.8.0 | Negative active energy (A-) total | Wh | 1 second |
8. | 1-0:3.8.0 | Positive reactive energy (R+) total | VArh | 1 second |
9. | 1-0:4.8.0 | Positive reactive energy (R-) total | VArh | 1 second |
10. | 1-0:14.7.0 | Frequency | Hz * 100 | 1 second |
11. | 1-0:31.7.0 | Instantaneous current (I) in phase L1 | A * 100 | 1 second |
12. | 1-0:51.7.0 | Instantaneous current (I) in phase L2 | A * 100 | 1 second |
13. | 1-0:71.7.0 | Instantaneous current (I) in phase L3 | A * 100 | 1 second |
14. | 1-0:32.7.0 | Instantaneous voltage (U) in phase L1 | V * 10 | 1 second |
15. | 1-0:52.7.0 | Instantaneous voltage (U) in phase L2 | V * 10 | 1 second |
16. | 1-0:72.7.0 | Instantaneous voltage (U) in phase L3 | V * 10 | 1 second |
17. | 1-0:21.7.0 | Positive active instantaneous power in phase L1 | W | 1 second |
18. | 1-0:41.7.0 | Positive active instantaneous power in phase L2 | W | 1 second |
19. | 1-0:61.7.0 | Positive active instantaneous power in phase L3 | W | 1 second |
20. | 1-0:22.7.0 | Negative active instantaneous power in phase L1 | W | 1 second |
21. | 1-0:42.7.0 | Negative active instantaneous power in phase L2 | W | 1 second |
22. | 1-0:62.7.0 | Negative active instantaneous power in phase L3 | W | 1 second |