How to connect HIQ PM3-E-D-CT energy meter with Reduxi controller
Connect your HIQ PM3-E-D-CT power sensor to the Reduxi Controller.
Text description of this image
Product photo of a white DIN-rail energy meter with a split-core current transformer (clamp) in front of it, on a white background. Meter: LCD showing 0000 kWh and a sigma sign with 031.4; four buttons at the right; symbols at the left; 'CE' mark and small print '3200imp/kWh 3K6 IEC62053-21 Cl.1, 3x230/400V 333mV 50/60Hz'. Current transformer: black clamp with a hinged opening, a grey cable coming out at the bottom left and a small label with text.
1 Technical documentation
Instructions to connect and configure the meter are on the HIQ manufacturer web page. Manufacturer documents of the HIQ PM3-E-D-CT:
- HIQ PM3-E-D-CT wiki page – Product description, interfaces, specifications and documents.
- PM3-E-D-CT user manual (PDF) – Installation, wiring and set-up menu.
- PM3-E-D-CT Modbus protocol v1.6 (PDF) – Modbus RTU protocol description.
2 Required equipment
- HIQ PM3-E-D-CT power sensor with current transformers (CT-3-E-xx, 0.33 V output), installed by a qualified electrician
- RS485 cable
- Reduxi Controller
- Laptop or tablet with internet access to configure the device in Reduxi
3 Connect and configure the meter
Find the instructions to connect and configure the meter in the documents of Point 1.
3.1 Interface and specification
The PM3-E-D-CT is a digital multi-function power sensor for single-phase and three-phase networks. It measures with current transformers (CT-3-E-xx, 0.33 V output). It connects to a three-phase four-wire (3P4W) supply.
The meter has an RS485 interface (terminals A and B) with the protocol Modbus RTU, semi-duplex.
3.2 Modbus settings on the meter
Set the Modbus parameters in the set-up menu of the meter, as described in the user manual:
1000 (see the user manual).The parity of the meter is none by default. You need the Modbus unit ID of the meter in the Reduxi Configurator. Normally, 1 is used.
4 Log in to the Reduxi web interface
You can open the Reduxi web interface in two ways:
Text description of this image
Screenshot of three Reduxi mobile app screens side by side, with cyan boxes and number badges 2 to 4. Left screen (dashboard, dark theme): menu icon at top left marked with a box and badge 2; 'reduxi' logo; tabs 'Real time data' (active) and 'Statistics'; price 5.79 € and temperature 3.2 °C; energy flow diagram with a house in the centre (-1.25 kW) and icons with values 69.0 W, 1.3 kW, 1.1 kW (red ring), -165.0 W with 97 % (red ring) and 0.0 W values at the bottom; tabs 'Power' and 'Energy'; bottom navigation: Dashboard, Diagnostics, Device control, Settings. Middle screen (side menu): 'reduxi' logo, 'Number of locations: 1233', heading 'Reduxi device management', entries '+ Add Reduxi location' and 'Reduxi devices' (marked with a box and badge 3), then 'My profile' and 'About app'. Right screen (device page): Back; picture of a black Reduxi controller with two Ethernet ports; status 'Connected'; card 'Update available': 'New update is available for your Reduxi device.' with button 'Download and install update'; card 'Connect to configurator': 'Tunnel connection enables remote access to your Reduxi configurator, without need to be connected to the same local network.' with button 'Activate tunnel connection' (marked with a box and badge 4); card 'Unit details' with field 'Unit ID'.
Text description of this image
Screenshot made of two parts side by side. Left part: Reduxi mobile app screen on a dark background. Top: Back button; picture of a black Reduxi controller with two Ethernet ports and a terminal block; status 'Connected' with a Wi-Fi icon. Card 'Update available': 'New update is available for your Reduxi device.' with button 'Download and install update'. Card 'Connect to configurator' with a key icon: 'Tunnel connection enables remote access to your Reduxi configurator, without need to be connected to the same local network.' and button 'Open configurator', marked with a cyan box and number badge 5. Below: card 'Unit details' with a field 'Unit ID' (value not visible). Right part: Reduxi Configurator opened in a browser, marked with a cyan frame and number badge 6. Header: back arrow, 'Tunnel connection', reload icon. Left sidebar with icons (lightning, chip, lightning bolt, bar chart, gear). Page 'Home' with a green link icon. Green notice: 'New patch available. Click here to apply.' with a close X. Time 09:12:56. Energy flow diagram with a house in the centre (1.700 kW) and icons for grid (0.000 kW), solar (1.700 kW), battery (green, 0.000 kW and 0.800 kW), a device at left (0.900 kW), electric vehicle and a charger or device at bottom. Label 'Energy manager' at the bottom.
http://reduxi.local. You can find the controller's IP address in your router's device list or in the Reduxi app under Reduxi devices.admin · Password: admin (factory default)Text description of this image
Screenshot of the Reduxi Configurator login page in a Chrome browser window. The address bar shows 'Not secure' and 'reduxi.local'; the address bar is marked with a cyan box and an enlarged copy of it (cyan box, text 'Not secure reduxi.local') is shown at the left, connected by a cyan line. Page background: light grey line drawing of a house with solar panels (green), a wall box, an inverter, a car and a charger. Top left: 'reduxi configurator' logo. Login box in the centre with title 'Login', a language selector (English flag, 'English'), a username field and a password field, and a dark 'Login' button.
Text description of this image
Screenshot of the Reduxi Configurator web interface after login, light theme. Top left: 'reduxi configurator' logo. Header bar: 'Home' at left, green 'Connected' status at top right. Left sidebar: expanded section 'Devices' with a list of entries, then collapsed sections 'Manager' and 'Configuration' and 'Settings'. Main area: energy flow diagram. House in the centre with ring, value 24.20 kW. Grid icon at top left, 24.20 kW (red dot on its line). Solar icon at top right, value '-'. Left icon (battery or device), 6.700 kW (green dot on its line). Right icons (battery storage and a device), values '-'. EV charger icon at bottom left, 31.00 kW. A further device icon at bottom right. Label 'Energy manager' below the house.
5 Add the meter to Reduxi
Use these steps to add a new meter or to edit an existing one.
5.1 Basic settings
Log in to the Reduxi Configurator via the browser (see Point 4) and click Add device.
In the first step, enter the basic settings of the device. Then click Next.
5.2 Communication settings
Select the communication channel. Then enter the device configuration:
| Parameter | Value |
|---|---|
| Modbus unit ID | Normally 1
|
Then enter and choose the advanced settings. Serial parameters, if requested, must match the settings of the meter (see Point 3).
5.3 Test communication
Click Test communication at the bottom of the wizard. It reads the HIQ PM3-E-D-CT once and saves nothing. If the test succeeds, click Done: only Done creates the device.
Text description of this image
Screenshot of the bottom button bar of a Reduxi Configurator page. Left: button 'Back'. Right: button 'Test communication' (marked with a cyan box) and dark button 'Done'.
Text description of this image
Screenshot of the Reduxi Configurator page 'Communication channel and device configuration'. Connection *: TCP/IP (dropdown). IP *: 192.168.50.243, with button 'Scan for IP'. Port *: 502, with button 'Test port'. Modbus unit ID *: 1. Buttons at the bottom: Back (left), Test communication and Done (right). The Done button is marked with a cyan box.
6 Check the readings
6.1 Last measurements
After communication is established, check the values under Devices in the Reduxi Configurator. Reduxi only reads the meter.
✓ Summary
Preparation (Points 1–2): Read the HIQ documents and prepare the equipment.
HIQ PM3-E-D-CT (Point 3): Connect the meter via RS485. Set the Modbus parameters and note the Modbus unit ID.
Add to Reduxi (Points 4–5): Log in to the Reduxi Configurator, add the meter with its Modbus unit ID and test the communication.
Go live (Point 6): Check the readings. Reduxi reads the meter.
→ Common issues
| Issue | Solution |
|---|---|
| Test communication fails | Check that the Modbus unit ID in Reduxi equals the address set on the meter (1 to 247). Check that the serial parameters match. |
| The meter does not respond on the RS485 bus | Check the RS485 lines A and B and the communication settings on the meter. |
| Open configurator does not open or stays empty | The tunnel is not active yet. Wait about 30 seconds and check that the controller is online. |
Login with admin is rejected |
The password was changed during installation. Ask the installer. The Reduxi account password does not work here. |
reduxi.local does not load |
Your device is not in the same network as the controller. Use the IP address or the tunnel connection. |