How to set-up Reduxi Controller with Reduxi Configurator
Set up the Reduxi Controller with the Reduxi Configurator: connect, add devices, control them manually or by strategy, and manage settings and users.
Text description of this image
Screenshot of the Welcome! page of the Reduxi Configurator, on a light background with a faint line drawing. Text: After initial configuration wireless access point will be disabled on the controller. We recommend you set up a static wired or wireless IP address. Section Network settings with tabs Wired network (selected), Wireless network, Mobile network; field Type: DHCP (dropdown). Section Network information (table): Ethernet IP: 192.168.1.200 (underlined link); Ethernet netmask: 255.255.255.0. Section Grid settings: Fuse L1: 16 A; Fuse L2: 16 A; Fuse L3: 16 A; Import power active limit: 11 kW; Export power active limit: 8.8 kW. Section Additional information: Unit ID: PMU8-KOZF-LC5C-2JEB (greyed out); Location: Test location; Timezone: Europe/Ljubljana (dropdown with clear and arrow icons). Button at the bottom right: Save configuration (black).
1 Introduction
The Reduxi Configurator is a web interface used to configure the Reduxi Controller.
With the Reduxi energy management system you can measure and analyse electricity consumption. Using special strategies, Reduxi enables you to optimize the use of electricity and to reduce its costs.
You recognize the Reduxi Configurator by a simple interface on a bright background.
To set up and operate the Reduxi system, you need to:
Old manuals are available at: Reduxi Configurator - old version, until 9th May 2025
2 Quick steps to connect the Reduxi Controller
As explained in the Reduxi Controller manual, do the following steps to connect to the controller and to open the Reduxi Configurator:
- Connect the AC-DC adapter to the Reduxi DC jack and plug it into a power outlet. The first top LED should turn on (green light).
- Set up the network connection (follow the instructions in Reduxi Controller).
- Open your browser and go to http://reduxi.local.
- You are redirected to the login page of the Reduxi Configurator.
- To log in to the Reduxi Configurator, enter the factory-set username and password:
| Field | Factory value |
|---|---|
| Username | admin |
| Password |
admin (or as printed on the label) |
After a successful login, we recommend changing the password of the user admin for security reasons. You can do it in your profile (see Point 10). You cannot change the username admin. However, you can create a new user with a new username.
3 Welcome screen of the Reduxi Configurator
The welcome screen invites the user to define the most important configurations to run the controller:
Text description of this image
Screenshot of the Welcome! page of the Reduxi Configurator, on a light background with a faint line drawing. Text: After initial configuration wireless access point will be disabled on the controller. We recommend you set up a static wired or wireless IP address. Section Network settings with tabs Wired network (selected), Wireless network, Mobile network; field Type: DHCP (dropdown). Section Network information (table): Ethernet IP: 192.168.1.200 (underlined link); Ethernet netmask: 255.255.255.0. Section Grid settings: Fuse L1: 16 A; Fuse L2: 16 A; Fuse L3: 16 A; Import power active limit: 11 kW; Export power active limit: 8.8 kW. Section Additional information: Unit ID: PMU8-KOZF-LC5C-2JEB (greyed out); Location: Test location; Timezone: Europe/Ljubljana (dropdown with clear and arrow icons). Button at the bottom right: Save configuration (black).
3.1 Network settings
To configure the network settings, follow the instructions in Reduxi Controller.
3.2 Grid settings
The limits of your electricity grid connection are essential for the reliable operation of your devices.
Provide the following two pieces of information:
- Rated current of the electrical fuse – the fuse (also known as a circuit breaker) protects your electrical system from excessive current.
- Import and export power limits
You can find this information on your electricity bill or in a document specifying your grid connection. If you have a single-phase power supply, enter only the L1 value.
The import and export limits are calculated automatically from the fuse rating. You can adjust them if necessary.
3.3 Name of the location and time zone
Enter a name that clearly identifies the location (for example Warehouse, Home, Site ABC) and select its time zone.
4 Main page of the Reduxi Configurator
After a successful login, you are redirected to the main page of the Reduxi Configurator. You can always return to the main page by clicking the Reduxi logo (top left).
On the main page you have access to:
Text description of this image
Screenshot of the main page (Dashboard) of the Reduxi Configurator. Top left: Reduxi Configurator logo. Left menu: section "Devices" (minus icon) with entries Huawei SUN2000, Iskraemeco AM550, OCPP 1.6 compatible charger and "Add device" (framed); then "Strategies" (plus icon), "Utility rate plan"; heading "SETTINGS" with Grid, Network, System (plus icon), Profile, Users, About (plus icon); a small left-right arrow icon at the bottom. Header: "Dashboard" and a green link icon at the top right; time 12:29:07 in the centre. The energy flow diagram has a central house icon in a dark ring with a red indicator and 7.300 kW. Connected by lines are: Grid, red indicator, 5.600 kW; Solar, green indicator, 1.600 kW; Other, red indicator, 1.200 kW; Battery storage (battery icon, 90 %), green indicator 0.200 kW and red indicator 0.000 kW; HVAC, red indicator, 6.100 kW; EV charger (greyed out), value "-". A dark tooltip near the bottom reads "Energy manager coordinator for PV, EVSE, battery and heat pump". Bottom right small grey text: "Test location | PMU8-KOZF-LC5C-2JEB".
4.1 Dashboard
The dashboard gives a quick overview of the power measurements for each added device category.
The time of the last measurement is shown at the top middle. It should change every few seconds if the connection to the Reduxi Controller is established.
Click a category to open the page with detailed data about the device that was first added to that category. For example, clicking the category Solar Power Plant opens the first device added in the Solar Power Plants category.
At the bottom of the dashboard you can turn a strategy on or off. Use this to switch to another strategy or to stop a strategy from controlling your devices.
4.2 Side menu
The side (left) menu gives access to:
- Devices
- Strategies
- Adding devices
- Adding strategies
- Utility rate plan (pricing plan of electricity)
- Settings
5 Devices
The dashboard on the main page gives an overview of the measurements collected by the Reduxi Controller from the connected devices. These devices typically include electricity meters, EV chargers, solar inverters, battery inverters and similar equipment.
Connecting devices to Reduxi with the Add device function is a crucial step. It enables Reduxi to read measurements from these devices and to control those that are controllable.
Before you add a device logically in the system, you must physically connect it to Reduxi, typically via Ethernet, Modbus, relays or other communication interfaces. Information about the physical connection of the devices is on our List of supported devices page.
In summary, the Add device step is the logical connection of a device to the Reduxi Controller after the physical connection has been made.
5.1 Adding devices
To add a new device, click the Add device button. The Add device wizard opens.
Text description of this image
Screenshot of the left menu of the Reduxi Configurator, with the Reduxi Configurator logo at the top. Menu entries from top: Devices (expanded, dark grey, with a minus sign); Add device (with a plus sign, highlighted by a white box with a black border and a red arrow pointing to it from the right); Strategies (plus sign); Utility rate plan; heading SETTINGS; Grid; Network; System (plus sign); Profile; Users; About (plus sign).
5.1.1 Step 1: Basic settings
Device type
You can choose among the following categories:
- Battery
- EV charger
- Emulator
- Energy meter
- HVAC (heating, ventilation and air conditioning, heat pump)
- Hybrid inverter
- Other
- Solar power plant
Text description of this image
Screenshot of the Add device wizard in the Reduxi Configurator. A progress bar at the top has two steps: 1 Basic settings (active, black circle) and 2 Communication channel (grey). Below, the section Basic settings with the field Device type * open as a dropdown list. The field shows the grey text Energy meter. List entries: Battery, EV charger, Emulator, Energy meter (highlighted dark), HVAC, Hybrid inverter, Other, Solar power plant.
Type
The Type field shows a list of devices with which the Reduxi Controller can communicate. The list of devices is on our website: Supported devices.
Category (advanced setting)
Usually the selected category is the same as the device type. In some cases you may want to define a different category.
The selected category does not define the operation of the device. The purpose of the Category parameter is to group (aggregate) data for measurement displays. Choose the right category for the selected device. If you choose the wrong category, your data is aggregated incorrectly.
Name
Enter any device name in the field.
Text description of this image
Screenshot of the Reduxi Configurator form titled Basic settings. Device type *: Energy meter (dropdown). Type *: Iskraemeco AM550 (dropdown). Name *: Iskraemeco AM550 (text field, grey text). Buttons at the bottom: Back (white, outlined) on the left and Next (black) on the right.
5.1.2 Step 2: Communication channel and device configuration
The Communication Channel defines how Reduxi communicates with the device. The fields are pre-filled according to the selected device type. Communication between the devices and the controller can take place via:
- TCP/IP
- Local serial port RS485 (serial communication)
- Reduxi Gateway
- UDP
The Device Configuration section appears for specific device types. Here you enter the specific information for each individual device. These fields may already be pre-filled, depending on the device type. In most cases you find this information in the manufacturer's instructions for the device you want to add. Additional help is on the Supported devices page.
After you have set all parameters correctly, click the Test communication button to check the connection between the Reduxi Controller and the device.
Text description of this image
Screenshot of the Reduxi Configurator form "Communication channel and device configuration". Fields: Connection *: TCP/IP (dropdown); IP *: 192.168.1.123; Port *: 502; Modbus unit ID *: 1. Buttons: Back (left), Test communication and Next (right, dark).
5.1.3 Communication test
After you have configured the device, use the Test communication button to test whether communication works.
The response is one of two results:
Case 1: Communication is working properly.
Text description of this image
Screenshot of a dialog titled "Test communication" with a close button (x) at top right. Green text in the content box: "Successful readout from device". Values listed: Error: false; Battery voltage: 53.34 V; Grid active power: 1077 W; PV export active energy: null Wh; PV voltage: null V; Load import active energy: 2293200 Wh; Grid import active energy: 2402100 Wh; PV current: null A; Battery state of charge: 88 %; Battery export active energy: 83000 Wh; Battery import active energy: 87400 Wh; Off-grid: false; Battery active power: -9 W; Battery min. active power: -10668 W; Load active power: 994 W; Battery current: -0.17 A; Battery max. active power: 5334 W; Grid export active energy: 100 Wh; State name: NORMAL; PV active power: null W; PV min. active power: null W; Inverter active power: 985 W. Button at bottom right: Close.
Case 2: Communication is not working properly.
Text description of this image
Screenshot of a dialog titled "Test communication" with a close button (x) at top right. One box with the text "Unable to communicate with device." Button at bottom right: Close.
If the communication does not work, check the settings you defined earlier. You might also need to configure the device (for example the inverter) to communicate via the selected interface.
5.1.4 Advanced configuration (optional)
Advanced configuration is available in the Details of the selected device. Mostly you do not need to fill in these fields. They are intended for users who specifically need advanced settings.
5.2 Editing configuration and deleting devices
To open the device configuration, click the corresponding device.
Text description of this image
Screenshot of the Devices page of the Reduxi Configurator. Left menu with the Reduxi Configurator logo: Devices (expanded, minus sign) with entries + Huawei SUN2000, + Iskraemeco AM550, + OCPP 1.6 compatible charger, + Add device (boxed), then Strategies (plus sign) and Utility rate plan. Main area titled Devices, with a green link icon at the top right. Three device cards. Card 1: Huawei SUN2000; Type: Huawei SUN2000; Categories: Battery, Grid, Solar power plant. Card 2: Iskraemeco AM550; Type: Iskraemeco AM550; Categories: Grid. Card 3: OCPP 1.6 compatible charger; Type: OCPP 1.6 - JSON; Categories: EV charger. Each card has a bin icon at the top right. Below the cards: button + Add device. Two red arrows: one points left at the Huawei SUN2000 menu entry, one points diagonally at the Huawei SUN2000 card.
Here you can edit individual settings for the selected device or delete the device (click the trash icon).
Details screen - configuration
The Details screen opens a page to review or edit the device configuration.
In the Basic Configuration form you can also specify the Location and Energy Direction parameters.
Text description of this image
Screenshot of the Details tab of a device in the Reduxi Configurator. Tabs: Last measurements, Analyze, Archive, Details (active). Left panel "General configuration": Name: Huawei SUN2000; Type: Huawei SUN2000 (dropdown); Categories: tags Battery, Grid, Solar power plant (each with x); Location: Sub (dropdown); Energy direction: Consumption and production (dropdown). Right panel "Advanced configuration (optional)", each a question with a toggle, all set to No: Do you want to set data saving interval? (Default: 1 min); Do you want to set reading delay? (Default: 1000 ms); Do you want to set writing delay? (Default: 1000 ms); Do you want to set power generation limits and capabilities?; Do you want to set power consumption limits and capabilities?; Do you want to set battery capacity?; Do you want to set min. battery SOC?; Do you want to set max. battery SOC?. The lower part of the picture is empty white.
Location
You can choose:
- Main electric meter
- Sub - other electric meter or other device
- None
The "Sub" meter parameter affects the grouping (aggregation) of data and the calculation of the final sum of individual measurements. It prevents the readings of the main meter and the other meter from being added up in the total consumption. Example:
The main meter measures the electricity consumption of the entire house. You have a garage in the house and you use another meter to measure the consumption in the garage. The garage is part of the house, so its consumption is already included in the measurements of the main meter. For the garage, select "Sub" meter. This prevents the measurements of the other meter from being added to the main meter and causing an incorrect calculation.
Energy direction
You can choose:
- Consumption
- Production
- Consumption and production
- None
The energy direction depends on the function of the individual device. For example, you select Consumption for devices that use energy.
In the Advanced Configuration form, certain fields are already pre-filled. In most cases the pre-filled fields ensure normal communication between the Reduxi Controller and the connected device. You do not need to fill in the other fields. They are intended for users who specifically need advanced settings.
Deleting a device
To delete an individual device, click the trash icon.
5.3 Display of device measurements
After you select a device, you can display its measurements under:
- Last measurements
- Analyses
- Archive
Text description of this image
Screenshot of the Reduxi Configurator device page for Huawei SUN2000 on the tab "Last measurements". Breadcrumb: Devices / Huawei SUN2000; a green link icon at the top right. Left sidebar under the Reduxi Configurator logo: section "Devices" (minus icon) with entries Huawei SUN2000 (bold), Iskraemeco AM550, OCPP 1.6 compatible charger, and "Add device" (framed); then "Strategies" (plus icon), "Utility rate plan", heading "SETTINGS" and "Grid". Tabs: Last measurements (active), Analyze, Archive, Details. Red arrows point at Last measurements, Analyze and Archive. Cards: "Control type" with buttons Auto (teal, selected) and Manual (dark), timestamp 09. 05. 2025 11:58:34. "Battery": Battery active power setpoint, unit kW, value empty, 09. 05. 2025 11:58:53. "Grid": Grid import active power limit, kW, empty, 09. 05. 2025 11:58:53; Grid export active power limit, kW, empty, 09. 05. 2025 11:58:53. "Other": Battery maximum capacity (Wh): 10.0 kWh, 09. 05. 2025 11:58:53; Communication error: ON, 09. 05. 2025 11:58:50; Control type: AUTO, 09. 05. 2025 11:58:53; Mode name setpoint: empty, 09. 05. 2025 11:58:53.
5.3.1 Last measurements
The Last measurements tab shows the last recorded measurements for the selected device. Measurements are obtained from each device and stored in the Reduxi Controller.
You can set the data refresh interval (top right).
Use this point for the last check that the device and the connection work properly.
Text description of this image
Screenshot of the Reduxi Configurator device page, tab Last measurements (tabs: Last measurements, Analyze, Archive; a search field at top right and a green connection icon). Small toggle at top left with a selected option. Below are six measurement panels with a label and a value with unit each. Left upper panel lists 11 values, among them -1.9, -27.48, 61.25, 3.7, 19.3, 56.00, 20.66, 99.2, 99.2, 0.2, 0.0. Middle upper panel has 4 small rows. Right upper panel shows 0.7 and 2,863.8. Left lower panel shows 1.5, NORMAL, OFF. Middle lower panel shows 1.9, 2.0, 0.0, OFF, 2,471.5, 0.1. Right lower panel shows OFF, AUTO, PEAK_SHAVING.
Once the device is successfully added in the Reduxi Configurator, you can monitor and control it via the Reduxi Cloud application or the mobile app Reduxi Mobile App.
The Last measurements menu also allows manual control of the device. This is described in 5.4 Manual control of device.
5.3.2 Analysis
In the Analysis tab you can view data for the selected device based on past measurements. The data is displayed as graphs. At the top left you choose the time period for which you want to display the data.
On each graph, click the buttons below the graph to filter the displayed data.
Text description of this image
Screenshot of the Analyze tab of a device in the Reduxi Configurator. Tabs: Last measurements, Analyze (active), Archive. Date range field at the top right: "12/16/2024, 00:00 ~ 12/16/2024, 23:59" with a calendar icon. Section "Power" with a line chart "Power [kW]". Vertical axis from 0.0 to 8.0 (ticks 0.0, 2.0, 4.0, 6.0, 8.0). Horizontal axis times from 00:34 to 15:33 in steps of about 1 hour 40 minutes (00:34, 02:13, 03:53, 05:33, 07:13, 08:53, 10:33, 12:13, 13:53, 15:33). Legend: Active power (red), Import active power (blue), Export active power (green). The blue Import active power line is near 0.0 until about 03:30, rises to about 4.0 until about 04:30, drops to 0.0, rises again to about 4.0 at about 05:15 and then stays between about 4.0 and 6.0 with short peaks up to about 6.0 until the end of the chart. The green line stays at 0.0. The red line is not visible.
5.3.3 Archive
The Archive tab stores all past data recorded by the Reduxi Controller for the selected device. The archive shows the data in a table and exports it in CSV format.
5.4 Manual control of device
By default a regulated device is controlled automatically via a strategy (Auto control type). The Last measurements tab also allows manual control of the device.
This is an example of an SG ready compatible HVAC device:
Text description of this image
Screenshot of a device page with tabs Last measurements (selected), Analyze, Archive. Top right: dropdown Without refreshing and a refresh button. Box Control type: four buttons Auto, Manual, Off, Boost; Boost is highlighted in light turquoise, the others are dark; timestamp 16. 12. 2024 16:08:39. Box Current: AC current L1: -0.79 A; AC current L2: -0.75 A; AC current L3: -0.92 A; PV current: -0.03 A. Box Voltage: AC voltage L1: 235.80 V; AC voltage L2: 237.00 V; AC voltage L3: 234.90 V; PV voltage: 747.10 V. Box Power: Active power: -0.0 kW; Export active power: 0.0 kW; Export active power limit: 16.0 kW; Import active power: 0.0 kW; Max. active power: 0.0 kW; Min. active power: -16.0 kW. Every value has the timestamp 16. 12. 2024 16:08:39.
And a hybrid inverter:
Text description of this image
Screenshot of the Reduxi Configurator device page for Fronius GEN24 on the tab "Last measurements". Breadcrumb: Device / Fronius GEN24; a green link icon at the top right. Tabs: Last measurements (active), Analyze, Archive. At the right of the tabs a dropdown "Each second" and a refresh button. Control cards: "Control type" with buttons Auto (dark) and Manual (teal, selected), timestamp 18. 12. 2024 15:43:07. "Grid import active power limit": empty input field with minus and plus buttons and unit kW. "Grid export active power limit": empty input field with minus and plus buttons, kW. "Battery active power setpoint": empty input field with minus and plus buttons, kW. Card "Mode name setpoint" with five dark buttons: Max. production, Self consumption, Max. consumption, Peak shaving, Setpoint. Cards below: "Battery": Active power setpoint, kW, 18. 12. 2024 15:45:52. "Grid": Import active power limit, kW, 18. 12. 2024 15:45:52; Export active power limit, kW, 18. 12. 2024 15:45:52. "Other": Communication error: ON, 18. 12. 2024 15:45:48; Control type: MANUAL, 18. 12. 2024 15:45:52; Mode name setpoint: empty, 18. 12. 2024 15:45:52.
When testing, note that the device itself also needs to be configured properly to accept instructions from an external device.
HVAC devices respond very slowly (approx. 15 min), so a device might not react immediately to the desired setpoint.
Depending on your choice in the Control type window, you can choose between the Auto and Manual control type:
- Auto: In Auto mode, all power limits (consumption and production on the grid) for the inverter come directly from a user-defined strategy. To learn how to set up strategies correctly, read the article How to Correctly Set Up Strategies (see Point 6).
- Manual: In Manual mode, the user sets all power limits for the inverter (consumption and production on the grid) directly. Once you select Manual mode, four additional options become available: Max. production, Self-consumption, Max. consumption and Peak shaving.
5.4.1 Max. production
Max. production is intended for situations where the user chooses to export as much energy to the grid as possible, taken either from PV or from battery storage.
The power limits for export and import from the grid are constrained by the two parameters in the right cards "Grid Export/Import active power limits".
Text description of this image
Screenshot of four control tiles in the Reduxi Configurator. Tile 1 "Control type": buttons Auto (dark) and Manual (highlighted teal, selected). Tile 2 "Mode name setpoint - last time": buttons Max. production (highlighted teal, selected), Self consumption, Max. consumption, Peak shaving (dark). Tile 3 "Grid export active power limit": minus button, value 0.0, unit kW, plus button. Tile 4 "Grid import active power limit": minus button, value 2.0, unit kW, plus button. Each tile has a small timestamp at the bottom right.
Case 1: There is not enough PV production.
- PV production is less than the Grid export active power limit
- and
- Battery storage SOC is above the minimum SOC
Then the battery storage is discharged to reach the Grid export active power limit.
Case 2: There is enough PV production.
- PV production covers the building consumption
- and
- PV production is more than the Grid export active power limit
- and
- Battery storage SOC is below the maximum SOC
Then the battery storage is charged with the exceeded power until it reaches the maximum SOC.
When the battery storage reaches the maximum SOC, PV production is limited so that it does not exceed the Grid export active power limit.
After the end of the PV production day, Case 1 applies again.
5.4.2 Self-consumption
Self-consumption is intended for situations where the user aims to balance export and import so that the net sum equals zero. The Reduxi Controller monitors net grid consumption and production, calculates the difference between them and acts accordingly.
The power limits for export and import from the grid are limited by the limits in the right cards "Grid Export/Import active power limits".
Text description of this image
Screenshot of four control tiles in the Reduxi Configurator. Tile 1 "Control type": buttons Auto (dark) and Manual (highlighted teal, selected). Tile 2 "Mode name setpoint - last time": buttons Max. production (dark), Self consumption (highlighted teal, selected), Max. consumption, Peak shaving (dark). Tile 3 "Grid export active power limit": minus button, value 0.0, unit kW, plus button. Tile 4 "Grid import active power limit": minus button, value 2.0, unit kW, plus button. Each tile has a small timestamp at the bottom right.
Case 1: There is not enough PV production.
- PV production is 0
- or
- PV production is less than the building consumption
- and
- Battery storage SOC is above the minimum SOC
Then the battery storage is discharged to reach the zero value on the grid active power. The Reduxi Controller discharges the battery storage to cover the building consumption down to the minimum SOC.
Case 2: There is enough PV production.
- PV production covers the building production
- and
- PV production is more than the Grid export active power limit
- and
- Battery storage SOC is below the maximum SOC
Then the battery storage is charged with the exceeded power until it reaches the maximum SOC.
When the battery storage reaches the maximum SOC, PV production is limited so that it does not exceed the Grid export active power limit.
After the end of the PV production day, Case 1 applies again.
5.4.3 Maximum consumption
Maximum consumption is intended for situations where the user decides to import as much energy from the grid as possible. This mode is typically used in combination with EVSE (Electric Vehicle Supply Equipment) and BSEE (Battery Storage Energy Equipment), so the user can increase power on demand.
The power limits for both export and import from the grid are limited by the limits in the right cards "Grid Export/Import active power limits".
Text description of this image
Screenshot of four control tiles in the Reduxi Configurator. Tile 1 "Control type": buttons Auto (dark) and Manual (highlighted teal, selected). Tile 2 "Mode name setpoint - last time": buttons Max. production, Self consumption (dark), Max. consumption (highlighted teal, selected) and Peak shaving (dark). Tile 3 "Grid export active power limit": minus button, value 0.0, unit kW, plus button. Tile 4 "Grid import active power limit": minus button, value 2.0, unit kW, plus button. Each tile has a small timestamp at the bottom right.
Case 1: Building consumption is less than the Grid import active power limit.
- Building consumption is less than the Grid import active power limit
- or
- Battery storage SOC is below the maximum SOC
- or
- EV is connected to the EVSE but not charging
Then the battery storage and the EV start charging to reach the Grid import active power limit, until the maximum battery storage SOC or EV battery SOC is reached.
Case 2: There is PV production.
- PV production is more than 0
- or
- Building consumption is less than the Grid import active power limit
- or
- Battery storage SOC is below the maximum SOC
- or
- EV is connected to the EVSE but not charging
Then all the energy produced by PV is used first by the EVSE or the battery storage. When both reach the maximum SOC, the energy is sent to the grid, but still not more than the set Grid export active power limit. The battery storage is not discharged until the building consumption is bigger than the PV production.
5.4.4 Peak shaving
Peak shaving is intended for situations where the user decides to limit the Grid import active power when the limit is reached. The Grid import active power limit is important. You set it with the two parameters in the right cards "Grid export/import active power limits".
Text description of this image
Screenshot of four control tiles in the Reduxi Configurator. Tile 1 "Control type": buttons Auto (dark) and Manual (highlighted teal, selected). Tile 2 "Mode name setpoint - last time": buttons Max. production, Self consumption, Max. consumption (dark) and Peak shaving (highlighted teal, selected). Tile 3 "Grid export active power limit": minus button, value 0.0, unit kW, plus button. Tile 4 "Grid import active power limit": minus button, value 2.0, unit kW, plus button. Each tile has a small timestamp at the bottom right.
Case 1: Building consumption is less than the Grid import active power.
- PV production is less than or equal to 0
- or
- Building consumption is more than the Grid import active power limit
- and
- EV is charging
- and
- Battery storage is above the minimum SOC
Then the battery storage starts discharging to cover the power for EV charging, so that the Grid import active power limit is not exceeded.
If no battery storage is available, the power of the EV charger is reduced so that the Grid import active power limit is not exceeded.
The battery is charged when the Grid export active power limit is reached and there is enough PV production.
6 Strategies
Strategies regulate individual devices according to measurements recorded by the Reduxi Controller. With strategies, you can limit the consumption of individual devices or groups of devices in the Reduxi Configurator. You limit the consumption by setting the values that devices must not exceed. You can choose among different strategies to optimize the energy consumption. Use priorities to define a hierarchy of strategies.
To add and manage a strategy, follow the dedicated article: Strategies for Reduxi Controller.
Strategies are the automatic control modes of the devices, as opposed to the manual modes described in 5.4 Manual control of device.
7 Utility rate plan
The utility rate plan shows the pricing plan of your electricity (including energy, network fees, supplier fee, etc.). Define the pricing plan in the Cloud application as described in Reduxi price lists. This menu shows the prices for the current day.
8 Settings
The Settings module gives access to all settings:
- Grid settings
- Network settings (internet)
- System
- Users
- etc.
8.1 Grid
Grid settings define the specifics of your electrical grid connection. For details see 3.2 Grid settings.
8.2 Network
The Network settings show how the Reduxi Controller is connected to the network (internet). The module lets you configure Reduxi according to your internal IT network rules. Here you select the connection method or set the communication method (Proxy).
Reduxi supports networking via:
- wired network (LAN)
- wireless network (Wi‑Fi)
Wired (LAN) and wireless (Wi‑Fi) network
If the Reduxi Controller is connected to the network via a wired network (LAN), you find the data about this connection under the Wired network tab.
Under the Wireless network tab you can connect the Reduxi Controller to the network via a wireless connection (Wi‑Fi). Find the wireless network by clicking the Scan button. Select the wireless connection and enter the password, if necessary.
Alternative server (Proxy)
If your environment requires a proxy server, configure the proxy server settings in the Proxy Server tab.
8.3 System
The System settings menu allows advanced configurations for more specific usage.
8.3.1 Identifier
The Identifier shows the system information that identifies the Reduxi Configurator and the Reduxi Controller. This menu also shows the UnitID (the ID of the Reduxi Controller). This ID is very important when solving issues with a specific location.
8.3.2 Open VPN
Open VPN is intended for remote support.
If you want remote assistance from our support team, you need to:
193.9.21.21 and TCP port 2002.If the Open VPN connection works, the IP address is displayed. Send the IP address to our support. With this IP, our support can access the Reduxi Controller via the Open VPN connection.
To disable remote access via Open VPN, close the firewall or remove the Open VPN configuration file.
8.3.3 Connector
The Connector module allows data from the web controller to be sent:
- via Cloud to our web application Reduxi,
- in MQTT - an indirect server for data; data can be sent to another application or database.
Connector/Cloud
If you want to see your Reduxi Controller in the Reduxi web app, connect it to the cloud here. The Reduxi web application gives an overview of measurements anywhere. Instructions for using the Reduxi web application are on our website support.reduxi.eu.
Connector/MQTT
For an MQTT connection, you need the access data of the MQTT server. Access to the MQTT server is possible via a certificate or authentication data. Here you can define in what format the data is sent to the MQTT broker.
On the MQTT server, depending on the configuration, you must allow access for the Reduxi Controller via the selected connection method.
See the following articles for more details: Example how to connect Reduxi Configurator with MQTT broker? and Reduxi Controller - MQTT API.
8.3.4 Configuration
Backup
The Configurator Backup module exports all configuration data from the Reduxi Controller to a Configuration Source File.
Restore
The Configurator Restore module restores configuration data to the Reduxi Controller from a Configuration Source File.
When importing configuration data, you can select the type of configuration data to import (Cloud connection, MQTT connection, Network, OpenVPN).
8.3.5 Distribution System Operator
This module allows you to select your distribution system operator. They are grouped by country.
8.3.6 Time
The Time module allows you to enter the time zone and the time server through which the Reduxi system updates the time.
If you have entered a valid NTP server and the Reduxi Controller has access to the internet, the date and time are updated at a certain time interval from the data obtained from the NTP server.
8.3.7 Update
The Update module allows you to update the Reduxi Configurator with an up-to-date software patch. Automatic update is possible (preferred option with the Stable channel). Manual update is also possible: our Reduxi support team performs it via remote assistance (Open VPN).
8.3.8 Reboot
The Reboot module allows you to reboot the Reduxi Controller. A reboot can fix certain issues in some cases. During the reboot, the Reduxi Controller is unavailable and does not record measurements.
8.3.9 Factory reset
The Factory Reset module allows you to reset the Reduxi Controller to factory settings ("Reset"). The reset deletes all data and resets the Reduxi Controller.
If you click factory reset, two windows open:
During a factory reset, the Reduxi Controller is unavailable and does not record measurements.
8.3.10 Tools
This menu contains basic tools for problem diagnostics:
- ping test to test the connection with the TCP/IP connected device
- TCP port test to test the ports of the TCP/IP connected device
9 Users
The Users module shows all users that have been added to the Reduxi Configurator.
The module allows you to:
9.1 Adding new user
To add a new user, click the New user button. The form for creating a new user appears. Fill in the required fields and save the new user.
9.2 Displaying and editing users
The Users module shows all added users.
To edit a user, click the pen icon at the far right of the selected user's row. The same form opens as when adding a new user.
9.3 Deleting users
You can delete users in the Users module. To delete, click the trash icon at the far right of the row of the selected user. You must always have at least one active user.
10 Profile
You find the Profile module in the side menu, bottom left. In your profile you can edit your name, surname and password. You cannot change your username once you create it. You can also change the language in the Profile section.
Privacy policy information is also in the Profile section.
✓ Summary
Connect (Points 1–3): Plug in the controller, open http://reduxi.local, log in as admin and set network, grid, location name and time zone on the welcome screen.
Devices and dashboard (Points 4–5): Add each device with Add device (basic settings, communication test), check Last measurements, then control it by strategy (Auto) or manually.
Strategies and prices (Points 6–7): Strategies control the devices automatically. The utility rate plan shows the prices for the current day.
Settings, users, profile (Points 8–10): Configure network, connector, time, update, backup and reset under Settings. Manage users and your own profile.
→ Common issues
| Issue | Solution |
|---|---|
| Login to the Reduxi Configurator fails | Check the username and password (admin / admin, or as printed on the label). If it still fails, perform a factory reset or contact support@reduxi.eu. |
| Device is not in the Type list | Update the Reduxi Controller to the latest version (see Point 8, 8.3.7 Update). If the device is still missing, contact support@reduxi.eu. |
| Test communication fails | Check the settings you defined. Configure the device (for example the inverter) to communicate via the selected interface. |
| Configurator does not reboot | Check the LEDs on the back of the controller and contact support@reduxi.eu. |